Automation, sensing and robotics • Re: solid state relay not working as i expected

$
0
0
- this SSR only switches AC loads
- load current is 0.1 A to 2A * For tests use a legacy bulb (no LED) with min 30W@220VAC
- load voltage is 75 to 264 VAC *, so not suitable for low voltage applications.
- disconnect the CH2 input wire for a moment. Then bridge DC+ to CH2 which should switch the load on. Remove bridge and connect CH2 as needed. Be careful as mains is nearby on same board.

* https://www.roboter-bausatz.de/media/pd ... asheet.pdf

Statistics: Posted by ghp — Sat Oct 26, 2024 6:40 am